白丝美女被狂躁免费视频网站,500av导航大全精品,yw.193.cnc爆乳尤物未满,97se亚洲综合色区,аⅴ天堂中文在线网官网

Safety mechanisms, wake up and shutdown methods in distributed power installations

專利號
US11888387B2
公開日期
2024-01-30
申請人
Solaredge Technologies, Ltd(IL Herzeliya)
發(fā)明人
Meir Adest; Guy Sella; Lior Handelsman; Yoav Galin; Amir Fishelov; Meir Gazit; Yaron Binder
IPC分類
H02J1/00; H02M1/32; H02M3/158; G01S3/786; H01L31/02; H02H3/20; H02J1/10; H02J3/46; H02M7/493; H04B3/54; H02J3/38; H02J7/35; H02M1/00
技術(shù)領(lǐng)域
inverter,power,string,voltage,islanding,grid,converter,in,signal,output
地域: Herzliya Pituah

摘要

A distributed power system including multiple DC power sources and multiple power modules. The power modules include inputs coupled respectively to the DC power sources and outputs coupled in series to form a serial string. An inverter is coupled to the serial string. The inverter converts power input from the serial string to output power. A signaling mechanism between the inverter and the power module is adapted for controlling operation of the power modules. Also, for a protection method in the distributed power system, when the inverter stops production of the output power, each of the power modules is shut down and thereby the power input to the inverter is ceased.

說明書

In order to legally be allowed to connect to the grid in each country, inverter 104,204 is preferably designed to comply with local electrical regulations. Electrical regulations typically dictate, among other things, the minimal and maximal voltages of the grid e.g. 220-260 root mean squares voltage V, and a range of permitted frequency, e.g. 45-55 Hz. Whenever the grid deviates from allowed values inverter 104,204 is required to disconnect from the grid. Disconnection from the grid is typically performed using software controlling inverter 104, 204 and control circuitry which constantly monitors grid parameters, e.g. voltage, frequency.

In system 10, solar panels 101 are directly connected (e.g. in series-parallel) to inverter 104. When an islanding condition is detected, inverter 104 is disconnected from the grid. Hence, inverter 104 stops drawing current and therefore panels 101 output a relatively high open circuit voltage typically 25% higher than the normal operating voltage. An open circuit voltage 25% higher than nominal working voltage is typically safe, (less than the allowed 600 VDC in the USA and 1000 VDC in Europe) which are typical ratings for inverters 104 designed to be able to handle the higher open circuit voltage.

In system 20, there are power converters 205 which “push” power to the output of converters 205. Under an islanding condition which has been detected by inverter 204, inverter 204 is shut down and current is not flowing between converters 205 and inverter 204. Consequently, in system 20, the open circuit voltage at the input to inverter 204, reaches dangerous voltages, higher than the open circuit maximum voltage ratings of inverters 104, 204.

權(quán)利要求

1
微信群二維碼
意見反饋